Distribution box installation of common problems and solutions

<

Distribution box in the installation, there will always be some seemingly small, but not endanger the problem, the following small list of some of our installation of distribution box will appear some common problems and the corresponding control measures and solutions Way for your reference.

First, distribution box installation common problems:

01 outdoor distribution box no measures to prevent rainwater

02 power into the box is not in place

03 concealed assembly box into the line at the part of the wire buried in the wall without the tube

04 The cables entering and leaving the power distribution box are not grounded

05 Cable steel armor into the distribution box (cabinet) and is not grounded

06 pipe nozzle is not handled , the pipe is not plugged after the cable through the tube

07 hanging (embedded) wall distribution box height does not meet the requirements

08 distribution box phase, zero, the ground busbar on the unmarked

09 Distribution box with zero ground mixed (shared bus)

10 Distribution box, cabinet ground wire used in series with each other

11 distribution box without leaving the amount of wiring , irregular

12 Distribution Boxes The distance between the appliances and the sides of the box is too close

13 Distribution box power wiring phase sequence is incorrect

14 Distribution box wiring crowded , and irregular cross

15 knocking out the excess box knockout hole

16 distribution box, cabinet in the incoming line do not repeat the grounding

17 boxes of ground wire and bolt specifications do not match

18 Displacement between the centerline of the buried tube and the box hole

19 cable does not hang signs

20 conductor through the distribution board , the board hole at the mouth without protection

21 multi-strand cord is not tin , wire without nose

22 electrical fasteners do not match , no anti-loosening device

23 wire, wire nose, spark between the bus

24 copper nose fixed in the aluminum row no transitional measures

25 Connect more than two wires to the same terminal

26 A hollowed-out distribution box on a 180 mm thick wall creates a hollowed-out drum on the back

27 Ground wire is insufficient in wire diameter

28 zero, grounding the ground connection in series

29 serves as a ground terminal row PEN fastening end

30 Protects multiple branches with one earth leakage protector

31 Wiring of incoming power cord is incorrect

32 busbar bolt installation direction is wrong

33 busbar section less than 4 × 25 mm2

34 busbar fasteners incomplete, not complete , exposed thread inadequate

35 with the switch power supply side of the bus as a bus stand bracket

36 A few wires are first twisted with each other and then connected with a desired contact by a wire

Work zero line does not cross the zero sequence current transformer

38 boxes, the cabinet does not prevent rodent access to measures