What happened to the abnormal sound of the high-voltage test transformer?

<

The high voltage test transformer will emit a continuous and uniform "click" sound during normal operation. If the generated sound is not uniform or there are other special sounds, it should be considered that the transformer is not operating properly, and the fault can be found out according to the sound and processed in time. There are mainly the following breakdowns:

Overvoltage occurred in the power grid. When a single-phase ground or electromagnetic resonance occurs in the power grid, the transformer sound is sharper than usual. When this happens, a comprehensive judgment can be made in conjunction with the instructions of the voltmeter.

Transformer overload operation. The load changes greatly, and because of the effect of harmonics, the intermittent sound of “wailing” or “grilling” occurs instantaneously in the high-voltage test transformer, and the pointer of the monitoring and measuring instrument swings, and the tone is high and the volume is large.

Loose clamps or screws. The sound is louder than usual and there is noticeable noise. However, if there is no obvious abnormality in the current and voltage, the internal clips or the screws that press the iron core may loosen, causing the vibration of the silicon steel sheet to increase.

Partial discharge of the transformer. If the transformer's drop-out fuse or tap-changer is in poor contact, there will be a "beep" sound; if the transformer's transformer casing is dirty, the surface enamel falls off or there is a crack and a "click" can be heard. If the internal partial discharge of the transformer or the electrical connection is bad, it will give out a "beep" or "click" sound, and this sound will change with the distance from the fault. At this time, the transformer should be immediately deactivated.

Short circuit in transformer winding. The sound of water boiling in the sound, and the rapid temperature change, oil level rise, it should be judged as a short circuit fault winding transformer failure, in severe cases there will be a huge roar, and then may be a fire. At this time, the transformer should be immediately disabled for inspection.

The transformer shell flashes and discharges. This sound occurs when the transformer winding high voltage causes the outlets to discharge from each other or when they are out of the enclosure flashover. At this time, the transformer should be deactivated.

Odor and color of explosion-proof explosion-proof tube explosion-proof membrane rupture: Explosion-proof tube explosion-proof membrane rupture will cause water and moisture to enter the transformer, resulting in the emulsification of insulating oil and transformer insulation strength.

Casing flashover discharge, casing flashover discharge will cause heat to cause aging, damage to the insulation and even an explosion.

Lead wires (wiring heads) and line cards are overheated and cause abnormalities. Casing terminal parts are loosened or lead wires are not slippery. The contact surface is oxidized so that the contact is overheated, the color becomes dark and the gloss is lost. The surface plating is also Destroyed.

Sleeve fouling causes an abnormality; casing fouling produces corona, flashover will occur ozone odor, cooling fan, burning of the oil pump will emit a burning odor.

In addition, excessive moisture absorption, gasket damage, too much water into the oil chamber and other reasons will cause moisture discoloration.

Abnormal oil temperature is found under normal conditions, the oil temperature is more than 10 degrees Celsius higher than usual or the load does not change and the temperature continues to rise (in the case of normal operation of the cooling device), you can determine the internal abnormality of the transformer. Mainly for:

Internal fault caused temperature abnormality. Its internal faults, such as windings or inter-layer short circuits, coil discharge to the enclosure, internal lead joint heating, iron core multi-point grounding to increase eddy current overheating, zero-sequence unbalanced current and other leakage flux through the formation of a loop with the iron tank heating Such factors as abnormal transformer temperature. When these conditions occur, gas or differential protection actions are also accompanied. When the fault is serious, it is also possible to inject the explosion-proof pipe or pressure relief valve. At this time, the transformer should be deactivated and repaired immediately.

Abnormal temperature caused by abnormal cooler operation. The cooler is not operating properly or has failed. For example, the submersible pump is out of operation, the fan is damaged, the radiator pipe is fouled, the cooling effect is not good, the radiator valve is not opened, the thermometer indicates a failure, etc. Perform maintenance and flushing to improve its cooling effect.

High-voltage test abnormal transformer oil level during the operation of the oil level abnormalities and leakage of oil is more common, should be patrolling and inspections from time to time, which mainly has the following two aspects.

1, false oil level: oil standard tube plugging; oil pillow sucker plug; explosion-proof pipe plugging.

2. Low oil level: The transformer is seriously leaking oil. Workers are unable to replenish the oil due to work needs. The temperature is too low and the oil volume is insufficient, or the capacity of the pillow is too small to meet the demand for operation.

‎Multi Process Welder

1. The guide rail is rectangular;
2. It has the characteristics of large bearing capacity, good stability and low deflection.
3. Use the fork to lock the column device to prevent the skateboard and the beam from falling, to prevent the accident from causing the beam to fall.